Liquid-cooled Integrated ESS
Y104R04C12 — 5.015MWh
| General | |
|---|---|
| Product Model | Y104R04C12 |
| Configuration | 416s12p |
| Communication Protocol | CAN / RS485 / TCP/IP |
| Elevation | ≤ 3000 m |
| Cooling and Heating Type | Liquid Cooling / Heating |
| Operating Ambient Temp | −30 °C ~ 55 °C |
| Electrical Parameters | ||
|---|---|---|
| Withstand Voltage | 4500 VDC, leakage current ≤5 mA | |
| Short Circuit Current | 130.56 kA @12 racks | 13.6 kA @1 rack |
| Rated Energy | 5015.9 kWh | 100% DOD, 0.5P |
| Rated Voltage | 1331.2 V | |
| Operating Voltage Range | 1040 – 1500 V | |
| Rated Charge Power | 2500 kW (0.5P) | According to power map |
| Rated Discharge Power | 2500 kW (0.5P) | According to power map |
| Short Peak Charging Power | 5000 kW @60s | According to power map |
| Short Peak Discharging Power | 5000 kW @60s | According to power map |
| Auxiliary Power Supply |
3-phase 400 Vac ±10%, 50 Hz (CE) 3-phase 480 Vac ±10%, 60 Hz (UL) | |
| DC Side Output Form | 1 / 2 / 12 outputs (optional) | |
| Mechanical Parameters | |
|---|---|
| Mass | ~44.5 t |
| IP Level of Enclosure | IP55 |
| Dimension | 6058 × 2438 × 2896 mm (L × W × H, 20HQ) |
| Certification | |
|---|---|
| Executive Standard |
UL9540A-2019, UN38.3, RoHS, GB/T36276-2023 UL9540A-2019, UL1973-2022, IEC62477-1-2012 IEC62619-2022, IEC63056-2020, IEC60730-1-2022 UL9540-2023, NFPA68-2023, NFPA69-2024, NFPA855, UN3536 IEC62933-5-2-2022, ISO3744-2010, REACH |
5.015 MWh
High Energy
10000 + cycles
Long Cycle Life
High Safety
FSS with module-level and container-level protection
20HQ
Standardization
3 °C
Intelligent Temperature Control
Low LCOS
Scientific Design
27 % Land Saving
Single-side Door Opening Design
Seismic Resistance
Meet high design level based on IEEE Std 693
< 75 dB
Low Noise Design
Thermal Safety & System Reliability
UL9540A thermal spread test results demonstrate excellent performance. The system features combustible gas monitoring, pressure relief, and explosion protection compliant with NFPA 68/69 standards.
“2+2” fire control measures: modular built-in fire suppression combined with a container firefighting system arranged in an echelon configuration.
Thermal management: centralized cooling with multistage shunt, parallel flow channels, and throttling control. Module cell temperature difference ≤2 °C; container level ≤3 °C.
Battery system: special energy storage battery with 10,000+ cycles and a 20-year service life.
Protection design: enclosure rated IP55, anti-corrosion grade C4/C5, and high-voltage modules with IP67 protection.